
The MR-2312-DDR is equipped with 12 Class "B" (Style "B") initiating circuits and four Class "B" (Style "Y") indicating circuits at 1.7A maximum. (Total of 5A). Two MR-2300-A 6-Initiating Circuit Class A Converter Modules may be used for Class "A" (Style "D") wiring of the initiating circuits. One MR-2300-NC4 4-Indicating Circuit Class "A" Converter Module may be used for Class "A" (Style "Z") wiring of the Indicating circuits.
Main Features
- Front panel and PC programmable
- Remote upload / download capabilities
- Audible signals may be configured for Steady, Temporal Code, California Code and March Time
- Relay contacts for Common Alarm, Auxiliary / Alarm (Disconnectable), Common Supervisory and Common Trouble
- Configurable Signal Silence Inhibit, Auto Signal Silence and One-Man Walk Test
- Subsequent Alarm, Supervisory, and Trouble operation
- 5A Power Supply